ASTRAL Swirl Diffusers are designed to create a
rotary swirling motion to the supply air discharge,
which rapidly induces the room air to quickly
decrease the velocity and temperature difference of the supply air.
Swirl diffusers are used for ceiling or exposed duct mounting. Specially designed for spaces where considerable temperature changes take place and with ceiling heights of more than 4m, where high comfort standards are required. It can be used for commercial (conference rooms, auditoriums, etc.) or industrial installations (industrial halls, airports, theatres, bank buildings, shopping malls, exhibition halls, etc).
Heating, Cooling or isothermal air can be supplied by an adapted air pattern. Cold air has a tendency to ‘drop’, making it advisable to spread that air horizontally. Warm air however, can remain too close to the ceiling, not reaching the occupied zone. The variable swirl diffuser M-SWD, which can handle supply temperature differences of -10K up to +15K, can solve those problems.
Swirl diffusers are used for ceiling or exposed duct mounting. Specially designed for spaces where considerable temperature changes take place and with ceiling heights of more than 4m, where high comfort standards are required. It can be used for commercial (conference rooms, auditoriums, etc.) or industrial installations (industrial halls, airports, theatres, bank buildings, shopping malls, exhibition halls, etc).
Heating, Cooling or isothermal air can be supplied by an adapted air pattern. Cold air has a tendency to ‘drop’, making it advisable to spread that air horizontally. Warm air however, can remain too close to the ceiling, not reaching the occupied zone. The variable swirl diffuser M-SWD, which can handle supply temperature differences of -10K up to +15K, can solve those problems.
Features
- The variable air pattern swirl diffuser having a set of movable inner vanes to alter the angle of discharge from horizontal to vertical, which is imperative to ensure optimum heating and cooling function.
- Blades are adjusting by turning inner core, varying throw discharges can be achieved from fully horizontal to vertical projection, which is important in the heating mode.
- The Blade angles can be adjusted to 45 deg. to accomplish this adjustment two types of control are offered, manual or electric motor operation is also possible.
- Mounting heights of between 3 m to 12m, where large air volumes and temperature differentials are required.
- Frame and Blades are made of Extruded Aluminium.
- Nominal Sizes: 200, 250, 315, 350, 400, 500, 630
- Volume flow range: 19 lps - 11100 lps
- Installation can be flush with the ceiling or freely suspended.
- Available in different powder coated RAL finish
Rear View AS-SWD
Product Dimension
| Product Code | Description | Neck Ø | Face Ø | Hole Ø | Height H |
|---|---|---|---|---|---|
| AS-SWD200 | Round Swirl Diffuser - 12 Blade | 200 | 320 | 275 | 185 |
| AS-SWD250 | Round Swirl Diffuser - 12 Blade | 250 | 365 | 320 | 185 |
| AS-SWD315 | Round Swirl Diffuser - 12 Blade | 315 | 445 | 385 | 215 |
| AS-SWD350 | Round Swirl Diffuser - 12 Blade | 350 | 505 | 445 | 215 |
| AS-SWD400 | Round Swirl Diffuser - 12 Blade | 400 | 565 | 505 | 230 |
| AS-SWD500 | Round Swirl Diffuser - 12 Blade | 500 | 720 | 605 | 260 |
| AS-SWD630 | Round Swirl Diffuser - 12 Blade | 630 | 875 | 760 | 310 |
Performance Table: Swirl Diffuser
| Product Code | Pressure (Pa) | 5 | 10 | 20 | 30 | 40 | 50 | 60 | 70 |
|---|---|---|---|---|---|---|---|---|---|
| AS-SWD200 | Flow Rate (l/s) | 19 | 29 | 41 | 51 | 60 | 67 | 71 | 75 |
| Noise NR | <20 | <20 | <20 | <20 | 22 | 28 | 36 | 39 | |
| Throw 0° (m) | 0.4 | 0.8 | 1.6 | 2.2 | 2.7 | 3.1 | 3.4 | 3.6 | |
| AS-SWD250 | Flow Rate (l/s) | 33 | 50 | 71 | 88 | 101 | 114 | 123 | 130 |
| Noise NR | <20 | <20 | <20 | 21 | 26 | 32 | 38 | 41 | |
| Throw 0° (m) | 0.7 | 1.2 | 2.1 | 2.8 | 3.2 | 3.6 | 3.9 | 4.2 | |
| AS-SWD315 | Flow Rate (l/s) | 66 | 89 | 126 | 153 | 175 | 198 | 217 | 235 |
| Noise NR | <20 | <20 | 22 | 26 | 30 | 35 | 38 | 40 | |
| Throw 0° (m) | 1.1 | 1.7 | 2.7 | 3.3 | 3.8 | 4.2 | 4.6 | 5.1 | |
| AS-SWD350 | Flow Rate (l/s) | 83 | 112 | 155 | 193 | 222 | 249 | 271 | 294 |
| Noise NR | <20 | <20 | 21 | 31 | 35 | 39 | 40 | 42 | |
| Throw 0° (m) | 1.2 | 1.9 | 2.9 | 3.6 | 4.1 | 4.6 | 5.1 | 5.6 | |
| AS-SWD400 | Flow Rate (l/s) | 105 | 151 | 210 | 257 | 293 | 330 | 363 | 392 |
| Noise NR | <20 | <20 | 22 | 29 | 32 | 36 | 39 | 42 | |
| Throw 0° (m) | 1.3 | 2.0 | 3.1 | 3.7 | 4.3 | 4.8 | 5.4 | 5.9 | |
| AS-SWD500 | Flow Rate (l/s) | 142 | 222 | 347 | 423 | 472 | 527 | 583 | 638 |
| Noise NR | <20 | 25 | 32 | 35 | 37 | 39 | 41 | 43 | |
| Throw 0° (m) | 1.8 | 3.5 | 4 | 4.5 | 5.2 | 7 | 8.1 | 12 | |
| AS-SWD630 | Flow Rate (l/s) | 175 | 256 | 412 | 505 | 610 | 715 | 870 | 1100 |
| Noise NR | <20 | 26 | 34 | 37 | 40 | 44 | 47 | 52 | |
| Throw 0° (m) | 2.3 | 3.8 | 4.1 | 7 | 11 | 13 | 15 | 18 |
- Terminal velocities for throw = 0.25m/sec.
- Swirl diffuser ceiling mounted and blades set for maximum horrizontal throw.
- This data to be used for quick selection only, not to be used for commissioning.
Installation: Swirl Diffuser with Plenum Box
Swirl Diffuser Adjustable
Increasingly stringent requirements from the
standpoint of technical features (higher supply
flow rates and lower velocities in the occupant
area) and aesthetics (smoother incorporation in
the interior design) have generally made swirl
diffusers a better choice for air diffusion.
The recommended mounting height is around
2.5 to 4.0m for all models. All these ASTRAL units
can be used in VAV systems, allowing the flow
rate to be reduced up to 25% of the nominal air
flow rate without producing uncomfortable air
currents in the facility.
Features
- Powder coated white as standard
- A high quality diffuser to generate airflow according to the principle of turbulent mixed airflow
- Low sound power level and pressure loss
- Installation for prefabricated ceiling or surface mounted for closed false ceilings

Front Face

Back Face

Front Face
| Face Size (A) | No. of Blade |
|---|---|
| 595 x 595 mm | 16 |
| 595 x 595 mm | 24 |
| 595 x 595 mm | 48 |
- Diffusers are powder coated white as standard
- The first number is for horizontal dimension and the second number for vertical dimension.
Performance Table: Fixed Vane with Air Stream between Diffusers
| Flow rate | No. of slots | 16 | 24 | 32 | 36 | 40 | 48 | ||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| (m³/h) | (l/s) | B | 1.2 | 1.8 | 2.7 | 1.2 | 1.8 | 2.7 | 1.2 | 1.8 | 2.7 | 1.2 | 1.8 | 2.7 | 1.2 | 1.8 | 2.7 | 1.2 | 1.8 | 2.7 | |
Symbols:
- B - Distance between Diffusers
- H - Room height (m)
- Vz - Air flow velocity in occupied area (m)
- Pressure ( Pt) - All pressures are in Pa (N/m2 )
- NR - Noise level index in dB based on a room absorption and one diffuser
Performance Table: Fixed Vane with Air Stream towards the wall
| Flow rate | No. of slots | 16 | 20 | 24 | 32 | 36 | 40 | 48 | ||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| (m³/h) | (l/s) | B | 1.2 | 1.8 | 2.7 | 1.2 | 1.8 | 2.7 | 1.2 | 1.8 | 2.7 | 1.2 | 1.8 | 2.7 | 1.2 | 1.8 | 2.7 | 1.2 | 1.8 | 2.7 | 1.2 | 1.8 | 2.7 | |
Symbols:
- B - Distance between Diffusers
- H - Room height (m)
- Vz - Air flow velocity in occupied area (m)
- Pressure ( Pt) - All pressures are in Pa (N/m2 )
- NR - Noise level index in dB based on a room absorption and one diffuser
Fixed Vane Swirl Diffuser with number of deflectors

400/16

600/36

400/16

400/16

500/20

600/40

500/20

500/20

600/16

600/48

600/36

600/36

600/20

825/60

600/48

600/48

300/9

500/24

600/32
Fixed Blades Swirl Diffuser

AS-SW-F

AS-SW-F

Front Face

Back Face
| Face Size ( A ) | No. of Blade |
|---|---|
| 595 x 595 mm | 34 |
- Diffusers are powder coated white as standard
- The first number is for horizontal dimension and the second number for vertical dimension.
Performance Table: Fixed Blade
Inlet Size 6"
| Neck Velocity | 300 | 400 | 500 | 600 | 700 | 800 | 900 | 1000 |
|---|---|---|---|---|---|---|---|---|
| VP | 0.006 | 0.01 | 0.016 | 0.022 | 0.031 | 0.04 | 0.05 | 0.062 |
| Total Pressure | 0.01 | 0.018 | 0.028 | 0.04 | 0.054 | 0.071 | 0.09 | 0.111 |
| CFM | 59 | 79 | 98 | 118 | 137 | 157 | 177 | 196 |
| NC (dB) | – | – | – | – | 20 | 23 | 25 | 28 |
| Throw (ft) | 1-1-2 | 1-1-2 | 1-1-3 | 1-2-4 | 1-2-4 | 2-2-5 | 2-3-5 | 2-3-6 |
Inlet Size 8"
| Neck Velocity | 300 | 400 | 500 | 600 | 700 | 800 | 900 | 1000 |
|---|---|---|---|---|---|---|---|---|
| VP | 0.006 | 0.01 | 0.016 | 0.022 | 0.031 | 0.04 | 0.05 | 0.062 |
| Total Pressure | 0.017 | 0.03 | 0.047 | 0.068 | 0.092 | 0.12 | 0.152 | 0.188 |
| CFM | 105 | 140 | 174 | 209 | 244 | 279 | 314 | 349 |
| NC (dB) | – | – | – | 19 | 22 | 25 | 28 | 30 |
| Throw (ft) | 1-2-3 | 1-2-4 | 2-3-5 | 2-3-6 | 2-4-7 | 3-4-7 | 3-5-8 | 3-5-8 |
Inlet Size 12"
| Neck Velocity | 300 | 400 | 500 | 600 | 700 | 800 | 900 | 1000 |
|---|---|---|---|---|---|---|---|---|
| VP | 0.006 | 0.01 | 0.016 | 0.022 | 0.031 | 0.04 | 0.05 | 0.062 |
| Total Pressure | 0.048 | 0.086 | 0.134 | 0.194 | 0.264 | 0.344 | 0.436 | 0.538 |
| CFM | 236 | 314 | 393 | 471 | 550 | 628 | 707 | 785 |
| NC (dB) | – | – | 19 | 23 | 26 | 29 | 32 | 34 |
| Throw (ft) | 2-4-7 | 3-5-8 | 4-6-8 | 5-7-9 | 5-7-10 | 6-8-11 | 7-8-11 | 7-8-12 |
Inlet Size 14"
| Neck Velocity | 300 | 400 | 500 | 600 | 700 | 800 | 900 | 1000 |
|---|---|---|---|---|---|---|---|---|
| VP | 0.006 | 0.01 | 0.016 | 0.022 | 0.031 | 0.04 | 0.052 | 0.064 |
| Total Pressure | 0.082 | 0.146 | 0.228 | 0.328 | 0.446 | 0.583 | 0.748 | 0.912 |
| CFM | 321 | 428 | 535 | 641 | 748 | 855 | 962 | 1070 |
| NC (dB) | – | – | 20 | 24 | 27 | 30 | 33 | 35 |
| Throw (ft) | 3-5-8 | 4-6-9 | 5-7-10 | 6-8-11 | 7-8-12 | 7-9-12 | 8-10-13 | 9-11-14 |
Inlet Size 16"
| Neck Velocity | 300 | 400 | 500 | 600 | 700 | 800 |
|---|---|---|---|---|---|---|
| VP | 0.006 | 0.01 | 0.016 | 0.022 | 0.032 | 0.04 |
| Total Pressure | 0.139 | 0.247 | 0.385 | 0.555 | 0.772 | 0.988 |
| CFM | 419 | 558 | 698 | 837 | 978 | 1118 |
| NC (dB) | – | – | 21 | 25 | 28 | 31 |
| Throw (ft) | 4-6-9 | 6-7-10 | 6-8-11 | 7-9-12 | 7-10-13 | 8-11-14 |
Performance Notes:
- Tested In accordance with ASHRAE Standard 70-2006 - “Method of Testing for rating the Performance of Air Outlets and Inlets”.
- Airflow is in cubic feet per minute, CFM
- All pressures are in inches of water.
- VP - Velocity Pressure
- Throw values are given in feet to terminal velocities of 150-100-50 fpm.
- Throw data is based on supply air and room air at isothermal conditions.
- The NC values, sound pressure level, are based on a room absoption of 10 dB re 1012 watts and one diffuser.
- Blanks “-” indicate an NC level below 15.