Disc Valve
Astral Air Conditioning Industry LLC > Disc Valve
Disc Valve
Disc Valves are manufactured from high-quality steel with a polyester powder-coated finish, and are widely used for supply and exhaust air in washrooms and similar areas. The centre core is adjustable by screw and nut for precise air volume control, while the outer frame is fitted with a foam rubber gasket. Offering considerable cost advantage over conventional grilles and diffusers without compromising performance or aesthetics, they are also easy to adjust, maintain and clean.
Features
- Manufactured from high-quality steel with polyester powder-coated finish.
- Centre core adjustable by screw and nut for air volume control.
- Outer frame fitted with a foam rubber gasket.
- Type MDV disc valves suit all types of ventilation systems handling relatively low air volumes.
- Available in supply air (Model MSDV) and extract air (Model MEDV) constructions.
- Air volume flow rate can be changed by rotating the central disc.
- Easy adjustment, maintenance and cleaning.
Disc Valve M - DV
| Disc Valve Dimensions ‘Inches’ |
|||||||
|---|---|---|---|---|---|---|---|
| Nominal Size | A Ø | B Ø | C Ø | D Ø | E | F | G Ø (Opening Size) |
| 4" | 5 3/8 | 3 | 3 7/8 | 5 1/8 | 1 5/8 | 1 1/8 | 4 1/8 |
| 6" | 8 | 4 3/4 | 5 7/8 | 7 | 2 | 1 1/8 | 6 1/8 |
| 8" | 9 7/8 | 6 1/4 | 7 3/4 | 9 1/8 | 2 1/2 | 1 1/8 | 8 1/8 |
Performance data for 4″, 6″ and 8″ disc valves at different centre disc settings. Rotate the central disc to the required setting to achieve the desired air flow, static pressure and noise level.
| Performance Table - Size 4" | ||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Setting | Air Flow (CFM) |
15 | 20 | 25 | 30 | 35 | 40 | 45 | 50 | 60 | 70 | 80 | 90 | 100 |
| -3/8" | SP | 0.3 | 0.6 | 1 | ||||||||||
| NC | <20 | 20 | 25 | |||||||||||
| -1/4" | SP | - | 0.2 | 0.4 | 0.6 | 0.8 | 1.1 | |||||||
| NC | - | <20 | <20 | 23 | 25 | 26 | ||||||||
| -1/8" | SP | - | - | 0.2 | 0.3 | 0.5 | 0.6 | 0.8 | 1 | |||||
| NC | - | - | <20 | <20 | 22 | 24 | 26 | 28 | ||||||
| 0 | SP | - | - | - | 0.2 | 0.3 | 0.5 | 0.6 | 0.8 | 1 | 1.2 | |||
| NC | - | - | - | <20 | 20 | 22 | 24 | 26 | 32 | 34 | ||||
| 1/8" | SP | - | - | - | - | 0.2 | 0.3 | 0.4 | 0.5 | 0.6 | 0.8 | 1.2 | ||
| NC | - | - | - | - | <20 | <20 | 22 | 24 | 26 | 32 | 38 | |||
| 1/4" | SP | - | - | - | - | - | 0.2 | 0.3 | 0.3 | 0.5 | 0.6 | 0.8 | 1.1 | |
| NC | - | - | - | - | - | <20 | <20 | 22 | 25 | 28 | 33 | 42 | ||
| 3/8" | SP | - | - | - | - | - | - | 0.2 | 0.3 | 0.3 | 0.5 | 0.6 | 0.8 | 1.1 |
| NC | - | - | - | - | - | - | <20 | <20 | 23 | 25 | 29 | 38 | 45 | |
| 1/2" | SP | - | - | - | - | - | - | - | 0.2 | 0.3 | 0.3 | 0.4 | 0.6 | 0.8 |
| NC | - | - | - | - | - | - | - | <20 | 20 | 25 | 26 | 32 | 38 | |
| Performance Table - Size 6" | ||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Setting | Air Flow (CFM) |
30 | 35 | 40 | 50 | 60 | 70 | 80 | 90 | 100 | 120 | 140 | 160 | 180 |
| -1/4" | SP | 0.3 | 0.5 | 0.6 | 1.4 | |||||||||
| NC | <20 | 21 | 24 | 32 | ||||||||||
| -1/8" | SP | - | 0.2 | 0.3 | 0.4 | 0.6 | 0.8 | 1.1 | ||||||
| NC | - | <20 | <20 | 21 | 25 | 31 | 34 | |||||||
| 0 | SP | - | - | - | 0.2 | 0.3 | 0.4 | 0.6 | 0.8 | 1 | ||||
| NC | - | - | - | <20 | 20 | 23 | 26 | 34 | 40 | |||||
| 1/4" | SP | - | - | - | - | - | - | 0.2 | 0.3 | 0.4 | 0.6 | 0.8 | 1.1 | |
| NC | - | - | - | - | - | - | <20 | <20 | 22 | 31 | 35 | 42 | ||
| 1/2" | SP | - | - | - | - | - | - | - | 0.2 | 0.3 | 0.4 | 0.6 | 0.8 | 1 |
| NC | - | - | - | - | - | - | - | <20 | <20 | 24 | 28 | 35 | 45 | |
| Performance Table - Size 8" | ||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Setting | Air Flow (CFM) |
40 | 50 | 60 | 70 | 80 | 100 | 120 | 140 | 160 | 180 | 200 | 220 | 240 |
| -3/4" | SP | 0.4 | 0.6 | 0.9 | ||||||||||
| NC | 22 | 31 | 35 | |||||||||||
| -5/8" | SP | - | 0.2 | 0.3 | 0.4 | 0.6 | ||||||||
| NC | - | <20 | 20 | 23 | 26 | |||||||||
| -3/8" | SP | - | - | 0.2 | 0.2 | 0.3 | 0.5 | 0.7 | ||||||
| NC | - | - | <20 | <20 | 22 | 28 | 33 | |||||||
| -1/4" | SP | - | - | - | - | - | 0.3 | 0.4 | 0.5 | 0.7 | 0.9 | |||
| NC | - | - | - | - | - | 22 | 26 | 30 | 34 | 38 | ||||
| 0 | SP | - | - | - | - | - | 0.2 | 0.3 | 0.3 | 0.5 | 0.6 | 0.7 | ||
| NC | - | - | - | - | - | <20 | 23 | 26 | 31 | 36 | 38 | |||
| 1/4" | SP | - | - | - | - | - | - | 0.2 | 0.2 | 0.3 | 0.4 | 0.5 | 0.6 | 0.7 |
| NC | - | - | - | - | - | - | <20 | 23 | 26 | 30 | 32 | 36 | 38 | |
| 3/8" | SP | - | - | - | - | - | - | - | - | 0.3 | 0.3 | 0.4 | 0.5 | 0.6 |
| NC | - | - | - | - | - | - | - | - | 23 | 26 | 28 | 32 | 35 | |
| 5/8" | SP | - | - | - | - | - | - | - | - | 0.2 | 0.3 | 0.3 | 0.3 | 0.4 |
| NC | - | - | - | - | - | - | - | - | <20 | 23 | 25 | 27 | 33 | |
| 3/4" | SP | - | - | - | - | - | - | - | - | - | 0.2 | 0.2 | 0.3 | 0.3 |
| NC | - | - | - | - | - | - | - | - | - | 23 | 24 | 25 | 28 | |
| 1" | SP | - | - | - | - | - | - | - | - | - | - | 0.2 | 0.2 | 0.3 |
| NC | - | - | - | - | - | - | - | - | - | - | <20 | 24 | 25 | |
- Setting - position of the central disc in inches.
- Air Flow - all air flow values are in CFM.
- SP - Static Pressure.
- NC - Noise Criteria.
Send Us A Message